The BAPI BA/CO-D-BB is a Duct Mounted Carbon Monoxide Sensor that uses an aspiration tube for duct air sampling.  This sensor provides great accuracy performance in electrochemical sensing even at low concentrations.  

The sensor features 10 seconds backlit whenever a button is pushed and an LCD display for easy access CO reading. Also, the sensor uses ppm as the unit of measurement.  

The carbon monoxide detection is up to 500 ppm.  Also, it has field selectable outputs of 0 to 5, 1 to 5, 0 to 10, and 2 to 10 VDC and does have a 3-wire 4 to 20 mA output.  The two SPDT Alarm Relay Switch setpoints are 25, 35, 50, 100, and 200 ppm CO concentrations.  Monitoring made easy, with the LED indicator that displays different colors such as green, yellow, and red representing the unit's status.

The sensor element is easily replaceable and self-tested with a service life of up to 7 years.  The alarm timer can be set from 0 to 10 minutes which holds the output relays that allow more fan run time CO removal.

 
LED LIGHT INDICATION
COLOR DESCRIPTION
Green CO measurement is below Alarm 1 or Alarm 2 levels
Solid Yellow Sensor Module is performing a self-test
Yellow Sensor Module failed self-test, replace the sensor module
Flashing Red  CO measurement exceeds the Alarm 1 or Alarm 2 setpoint
CO measurement exceeds the Alarm 1 & Alarm 2 setpoint
Unit is configured for mA output, but the loop resistance is incorrect. Troubleshoot connection.
Unit is configured for voltage output, but the output voltage is incorrect. Troubleshoot connection
Solid Red Sensor Module is loose or missing. Securely plug in a sensor module
Field Selectable Ranges 0 to 100, 0 to 200, 0 to 300 & 0 to 500 ppm
Alarm Relays 2 Independent, Dry SPDT (Form C); 2 Amps at 24 VAC/DC, Resistive; 140 VA Inrush, 48 VA Holding at 24 VAC
Alarm Relay Setpoints 25, 35, 50, 100 or 200 ppm
Response Time <80 seconds from 10% to 90% of range
Field Wiring Terminals Pluggable Screw Terminals 14 to 24 AWG
Alarm Timer 0, 1, 5 & 10 minutes
Agency RoHS, CE
Field Selectable Outputs 3-wire 4 to 20 mA; 0 to 5, 1 to 5, 0 to 10, 2 to 10 VDC
Environmental Operation Range 14 to 122°F (-10 to 50°C) • 5 to 95%RH Noncondensing
Power 18 to 28 VAC, 7.2 VA Max; 18 to 40 VDC, 180 mA Max