Danfoss 003L-602501 Automatic Bypass Valve 3/4" Straight Union
AVDO self-acting constant flow controls are used to maintain a minimum flow rate (e.g. through a low water content gas boiler) or to control differential pressure in a heating system.
The closing of radiator or zone valves due to reduced heating demand may result in low flow and increased system differential pressure (potentially dead heating pumps). AVDO valves
open with a falling system load and allow flow through a bypass line whenever the differential pressure through the valve exceeds set point; ensuring a minimum flow rate or a system
differential pressure at minimum system load.
AVDO:
• Opens on rising differential pressure.
• Setting differential pressure range of 0.725 -7.25 psi (0.05-0.5 bar).
• Designed for 145 psi (10 bar), max. 248°F (120°C).
• Operates without impulse tubes.
• Can be supplied with NPT or solder tail pieces.
Control Range | diff. pressure 0.725 to 7.25 psi |
---|---|
Max Differential Pressure | 7.25 PSI (0.5 bar) |
Operation Pressure | 145 PSI (10 bar) |
Max Flow Temperature | 248F (120C) |
Max Leakage When Closed | 0.22 GPM (0.05 m3/h) |
Download Product Information:
Q & A: Ask the Questions, share answers
Do you have questions about this product?