Honeywell MVN713A0000 Modulating Control Ball Valve Actuator
MVN 3Nm (27 lb-in) Control Valve Actuator is used with the VBN2 2-way and the VBN3 3-way Control Ball Valves to control hot and chilled water with glycol solutions up to 50% in heating, venting, and air conditioning (HVAC) systems to provide two-position or modulating functions.
Features
- Non-Spring Return
- Floating and modulating
- Space saving, click-on installation - no tool required
- Extendable position indicator for easy commissioning
- Available with or without cable
- Compatible with control ball valves from 1/2" to 1-1/4"
- Actuator can be mounted on the valve in any of four positions
- Sizes from 1/2 to 3 in. with internal (female) NPT connections.
- Equal percentage flow characteristic.
- Reduced B port CV for constant loop flow.
- Choice of factory-installed actuation: floating, modulating (2-10 V), spring return or non-spring return 2-Position, Spring Return Modulating/Floating.
- Field configurable for normally open or normally closed fail-safe position.
- Removable manual operating handle to control valve during installation or in an event of power failure.
- Actuator can be mounted on the valve in any of four orientations.
- Field-serviceable stem assembly.
- Wide range of CV choices from 0.33 to 266.
- Nickel-chrome plated brass or 316 stainless steel ball and stem.
Actuator Type: Valve
Rotational Stroke: 90° ±3°.
Fail Safe Mode: Non-spring return, Fail in place
Torque: 27 lb-in. (3 Nm).
External Auxiliary Switches Available: No
Supply Voltage: 24 Vac +20%, -15%, 24 Vdc
Power Consumption: 5 VA- Modulating; 1.5 VA - Floating; 6 VA - Fast Acting SPDT
Environmental Rating: NEMA2
Frequency: 50 Hz; 60 Hz
Mounting: Click-on installation – no tool required
Noise Rating at 1m (Maximum): 35 dB(A) max at 1 m [50 dB (A) for MVN643].
Materials: Plenum rated plastic housing
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Ambient Temperature Range: -4°F to 131°F (-20°C to 55°C)
Storage Temperature Range: -40°F to 176°F (-40°C to 80°C)
Timing: 90 sec. for MVN613 and MVN713; 30 sec. for MVN643
Electrical Connections: Field wiring 18 to 20 AWG to screw terminals, located under the removable access cover.
Humidity Ratings: 5% to 95% RH non-condensing.
Design Life (at Rated Voltage): 60,000 cycles; 1 cycle = 0°…90°…0°
Cable Specification: 18 AWG, Plenum Rated, 300 V, 10 A, 3 ft. length from end of access cover.
Environmental Protection Ratings: IP40.
Approvals: UL/cUL; UL60730