System Sensor WFD30-2EXP Waterflow Detector 3" Explosion Proof 450 PSI HVAC Heavy Duty Vane Type Waterflow Switch

System Sensor WFD30-2EXP Waterflow Detector 3" Explosion Proof 450 PSI

SKU: WFD30-2EXP
UNSPSC: 39122223
Rating:
Quantity Price Stock
Usually Ships 1 - 3 Weeks
Usually Ships 1 - 3 Weeks
$2,126.12     /ea
Usually Ships 1 - 3 Weeks
0
$0.00
0
$0.00
0
WFD30-2EXP

System Sensor WFD30-2EXP is an explosion-proof vane-type waterflow detector designed for automatic sprinkler systems in hazardous indoor and outdoor locations.

Compatible with 3-inch Schedule 10 through Schedule 40 steel pipe, it activates at flow rates from 4 to 10 GPM and supports static pressures up to 450 PSI.  Its NEMA 4 cast-aluminum enclosure protects dual synchronized SPDT contacts, while the sealed pneumatic retard mechanism helps reduce false alarms caused by pressure surges.

Visual switch activation simplifies testing, and field-replaceable components support easier maintenance in Class I, II, and III hazardous-location installations designed to meet NFPA 13 and NFPA 72 requirements.

Order today for dependable flow detection and durable performance in demanding environments.

 


Frequently Asked Questions
 
  • What is the System Sensor WFD30-2EXP used for?

The WFD30-2EXP detects water movement in automatic sprinkler piping and activates an electrical signal when the flow reaches its operating threshold. It is intended for alarm, monitoring, and control applications in hazardous locations.

  • What pipe size is compatible with the WFD30-2EXP?

This model is designed for 3-inch steel water pipe and is compatible with Schedule 10 through Schedule 40 piping. It installs through a 2-inch pipe hole.

  • What is the waterflow activation range?

The detector is designed to activate at waterflow rates between 4 and 10 GPM.

  • What is the maximum pressure rating?

The WFD30-2EXP supports a maximum static pressure of 450 PSI.

  • Can this detector be installed outdoors?

Yes. Its NEMA 4 cast-aluminum enclosure is rated for indoor and outdoor use and helps protect internal components from demanding environmental conditions.

  • Is the WFD30-2EXP approved for hazardous locations?

Yes. It is designed for Class I, Groups B, C and D; Class II, Groups E, F and G; and Class III locations, including Division 1 and Division 2 applications.

  • How does the retard mechanism help prevent nuisance alarms?

The field-adjustable, sealed pneumatic retard mechanism delays switch activation for a preset period, helping prevent temporary pressure surges from creating unwanted alarms. Its sealed design also helps protect the mechanism from dust and dirt.

  • What electrical contacts are included?

The detector contains two synchronized SPDT Form C switches rated at 10 A at 125/250 VAC and 2.5 A at 24 VDC.

  • What temperature range does it support?

The specified operating temperature range is 32°F to 120°F, or 0°C to 49°C.

  • Does the detector provide visual confirmation during testing?

Yes. Visual switch activation allows technicians to verify retard timing and operation, including in noisy installation environments.

  • What are the product dimensions and weight?

The overall dimensions are approximately 6 inches high × 9 inches long × 6.5 inches wide. The WFD30-2EXP weighs approximately 10.9 pounds.

  • Which sprinkler and alarm standards apply?

The detector is specified for automatic sprinkler service under NFPA 13 and fire alarm applications under NFPA 72. Installation should be completed according to applicable codes, approved plans, and manufacturer instructions.

 

Static Pressure Rating 450 PSI
Pipe Compatibility 3-Inch
Approvals UL Listed
Flow activation range 4 to 10 GPM
Switch configuration Two synchronized SPDT Form C contacts
Contact rating 10 A at 125/250 VAC; 2.5 A at 24 VDC
Conduit entrances Two openings for 1/2-inch conduit
Operating temperature 32°F to 120°F (0°C to 49°C)